设计简介 |
设计描述:
文档包括:
word版设计说明书一份,共84页,约18000字
任务书一份
翻译一份
CAD版本图纸,共16张
某法院行政办公楼
摘 要
本工程办公楼工程,采用框架结构,主体为五层,本地区抗震设防烈度为8度,近震,场地类别为II类场地。主导风向为西北,基本风压0.50KN/M,基本雪压0.35 KN/M。楼﹑屋盖均采用现浇钢筋混凝土结构。
本设计贯彻“实用、安全、经济、美观”的设计原则。按照建筑设计规范,认真考虑影响设计的各项因素。根据结构与建筑的总体与细部的关系。
本设计主要进行了结构方案中横向框架第3轴抗震设计。在确定框架布局之后,先进行了层间荷载代表值的计算,接着利用顶点位移法求出自震周期,进而按底部剪力法计算水平地震荷载作用下大小,进而求出在水平荷载作用下的结构内力(弯矩、剪力、轴力)。接着计算竖向荷载(恒载及活荷载)作用下的结构内力。是找出最不利的一组或几组内力组合。 选取最安全的结果计算配筋并绘图。此外还进行了结构方案中的室内楼梯的设计。完成了平台板,梯段板,平台梁等构件的内力和配筋计算及施工图绘制。对楼板进行了配筋计算,本设计采用住下条形基础,对基础进行了受力和配筋计算。
整个结构在设计过程中,严格遵循相关的专业规范的要求,参考相关资料和有关最新的国家标准规范,对设计的各个环节进行综合全面的科学性考虑。总之,适用、安全、经济、使用方便是本设计的原则。设计合理可行的建筑结构方案是现场施工的重要依据。
关键词: 框架结构,抗震设计,荷载计算,内力计算,计算配筋
office building
ABSTRACT
This works for the university of office building, a framework structure for a five-storey main, in the region earthquake intensity of 8 degrees near Lan site classification as Class II venues. Led to the southwest direction, the basic Pressure 0.50 KN / M, basic snow pressure 0.35KN/M. Floor roof were using cast-in-place reinforced concrete structure.
The design and implement "practical, security, economic, aesthetic," the design principles. With the architectural design, design seriously consider the influence of the various factors. According to the structural and architectural detail and the overall relationship.
The design of the main structure of the program horizontal framework 3-axis seismic design. In determining the distribution framework, the first layer of representative value of the load, Then use vertex from the displacement method for earthquake cycle, and then at the bottom of shear horizontal seismic load calculation under size, then calculated the level of load under the Internal Forces (bending moment, shear and axial force). Then calculate vertical load (constant load and live load) under the Internal Forces. Identify the most disadvantaged group or an internal force several combinations. Select the best safety results of the reinforcement and Mapping. In addition, the structure of the program indoor staircase design. Completion of the platform boards, boards of the ladder, platform beam component and the reinforcement of internal forces calculation and construction mapping. On the floor reinforcement calculation, the use of pile foundation design, foundation and pile caps for the force and reinforcement calculation.
The whole structure of the design process, in strict compliance with the relevant professional standard, reference to relevant information and the latest national standards and specifications, and design of the various components of a comprehensive scientific considerations. In short, application, security, economic and user-friendly design is the principle. Design reasonable and workable structure of the program is the construction site of the important basis for the construction.
KEY WORDS: Frame Structure,Seismic Design
Load Calculation
Internal force calculation
Calculation reinforcement
建筑设计
一、工程概况:
本工程是根据西安相关建设部门批准方案进行设计的,是某法院行政办公楼,等级为Ⅰ级,结构使用年限为50年,耐火等级为Ⅱ级,抗震设防烈度为8度;结构方案为框架结构。
二、设计资料:
西安市平均气温﹤25℃;属于西北地震带,6级;抗震设防烈度8度;设计基本加速度为0.1g。
地基承载力标准值为150KN/m;二类场地,地势平坦。
常年地下水位低于2.0米;水质对混凝土无侵蚀作用;土的渗透系数k=30m/昼夜。
三、设计依据:
《 办公建筑设计规范》 JGJ67-89
《建筑设计防火规范》 GBJ 16——68(2001)
《民用建筑设计通则》 JGJ 37——87
《建筑设计资料集》 (1)(4)
第一节 一般规定
办公建筑应根据使用性质、建设规模与标准的不同,确定各类用房。一般由办公用房、公共用房、服务用房等组成。
办公建筑应根据使用要求,结合基地面积、结构选型等情况按建筑模数选择开间和进深,合理确定建筑平面,并为今后改造和灵活分隔创造条件。
六层及六层以上办公建筑应设电梯。建筑高度超过75m的办公建筑电梯应分区或分层使用。
窗
一、底层及半地下室外窗宜采取防范措施。
二、高层办公建筑采用大面积玻璃窗或玻璃幕墙时应设擦窗设施。
三、设采暖空调的办公建筑,外窗面积在满足采光要求的前提下,应尽量减少;空调办公建筑外窗应有良好的密闭性和隔热性,全空调办公建筑外窗应设部分可开启窗扇。
门
一、办公室门洞口宽度不应小于1m,高度不应小于2m。
二、机要办公室、财务办公室、重要档案库和贵重仪表间的门应采取防盗措施,室内宜设防盗报警装置。
门厅
一、门厅一般可设传达室、收发室、会客室。根据使用需要也可设门廊、警卫室、衣帽间和电话间等。
二、门厅应与楼梯、过厅、电梯厅邻近。
三、严寒和寒冷地区的门厅,应设门斗或其它防寒设施。
走道
|